Fans can be classified into several types according to the materials used, such as iron shell fans (ordinary fans), glass fiber reinforced plastic fans, plastic fans, aluminum fans, stainless steel fans, etc. Centrifugal fan company In the direction of gas flow. Fans can be classified into centrifugal, axial, diagonal (mixed flow) and cross flow fans according to the direction of gas flow. (1) Centrifugal fan. The airflow enters the impeller of the fan axially and flows mainly along the radial direction. This type of fan is made according to the principle of centrifugal action, and its products include centrifugal fan, centrifugal blower and centrifugal compressor. (2) Axial flow fan. The airflow enters the impeller of the fan axially and flows approximately along the axis on the cylindrical surface. Such fans include axial fans, axial blowers and axial compressors. (3) Rotary fan. Shangrao major Centrifugal fan Use the rotor rotation to change the air chamber volume to work. Common varieties include Roots blower and rotary compressor.
When the bearing temperature of the fan is normal, it is ≤ 70 ℃. If it rises to 70 ℃, an alarm should (will) be given if there is an electric control. At this time, the reason should be found out. First, check whether the cooling water is normal? Is the bearing oil level normal? If the cause cannot be found for a while, the bearing temperature rises rapidly to 90 ℃, and if there is an electric control, the alarm and shutdown signal shall be sent again. Shangrao Centrifugal fan In the process of fan startup, shutdown or operation, if any abnormal phenomenon is found, it shall be checked immediately. If any small fault is found during the check, it shall be timely found out the cause and eliminated. In case of major fault (such as severe vibration, impact of fan, sharp rise of bearing temperature, etc.), stop the machine immediately for inspection. major Centrifugal fan The lubricating oil (or grease) shall be renewed and replaced one month after the first operation of the fan. In addition to replacement after each overhaul, the lubricating oil (or grease) can be replaced once every 1~2 months under normal conditions, or according to the actual situation. Fans include fans, turbine blowers, roots blowers and turbine compressors, which are divided into seven categories in detail, including centrifugal compressors, axial compressors, centrifugal blowers, roots blowers, centrifugal fans, axial fans and Ye's blowers
major Centrifugal fan Fans can be divided into axial flow fans, centrifugal fans and diagonal flow (mixed flow) fans according to the flow direction after the airflow enters the impeller. Fans are divided into press in local fans (hereinafter referred to as press in fans) and flame-proof motors placed outside or inside the flow channel, and flame-proof motors placed inside the explosion-proof sealing chamber of the extraction type local fans (hereinafter referred to as extraction fans) according to their purposes. Centrifugal fan company Fans can also be divided into single-stage, two-stage or multi-stage pressurization fans according to the form of pressurization. For example, 4-72 is single-stage pressurization, and high-end fan is multi-stage pressurization fan. Fans can be divided into axial flow fans, mixed flow fans, roof fans, air conditioning fans, etc. Fan can be divided into negative pressure fan, low pressure fan, medium pressure fan and high pressure fan according to pressure. According to the outlet pressure (pressure rise), it can be divided into: ventilator (≤ 15000 Pa), blower (15-350000 Pa), compressor (≥ 350000 Pa)
(1) Centrifugal fan company The operating environment should always be kept clean, the fan surface should be kept clean, and the air inlet and outlet should be free of sundries. Regularly remove dust and other sundries in the fan and pipe. (2) major Centrifugal fan It can only be operated when the fan is completely normal. At the same time, it is necessary to maintain sufficient capacity of power supply facilities and stable voltage. Open phase operation is strictly prohibited. The power supply lines must be dedicated lines, and temporary lines should not be used for long-term power supply. (3) In case of abnormal sound, serious heating of motor, electrification of shell, tripping of switch, failure to start and other phenomena of fan during operation, the fan shall be stopped immediately for inspection. To ensure safety, maintenance is not allowed during the operation of the fan. After the maintenance, the test run shall be carried out for about five minutes, and the machine shall be restarted after confirming that there is no abnormal phenomenon. (4) Shangrao Centrifugal fan company Replenish or replace lubricating grease for bearings irregularly according to the service environmental conditions (it is not necessary to replace lubricating grease for motor enclosed bearings within the service life). To ensure good lubrication of the fan during operation, the number of times of oiling shall not be less than 1000 hours/time. For enclosed bearings and motor bearings, fill 2/3 of the inner and outer rings of bearings with ZL-3 lithium based lubricating grease. It is strictly prohibited to run without oil. (5) The fan shall be stored in a dry environment to prevent the motor from moisture. Rain proof measures shall be taken when the fan is stored in the open air. The fan shall be prevented from collision during storage and handling to avoid damage to the fan.